The arrangement and connection of incoming and outgoing feeders in grid stations and substations and the number of busbars have a significant influence on the supply reliability of the power system. Grid stations and substations, and the topology of the power systems must be designed in a similar way and must therefore be included in the context of planning as a single task. We have several busbar arrangements employed in grid stations and substations; they include:
Contents
This is the simplest arrangement of a substation as illustrated in figure 1(a). The outgoing feeders are connected to a single busbar and a single transformer is installed.
Independently of the number of feeders supplied according to the topology of the system, no supply reserve exists for the outage of the transformer or of the busbar. The transformer can be loaded up to 100 % of its permissible (rated) load.
This arrangement is found in MV and LV systems but also in 110/10 kV systems where a three-winding transformer can be installed to feed two MV systems as illustrated below:
The arrangement with two transformers as illustrated in figure 1(c) offers a supply reserve for the outage of one transformer. If both transformers are loaded under normal operating conditions only to the extent that each one can take over the total load of the substation in case of outage of the other transformer, which is normally not substantially more than 50 % of the rated load.
If circuit breakers are installed in the outgoing feeders, short-circuits of the lines affect only the consumers attached to the faulted line, since the network protection disconnects the faulted line selectively. If load-break switches are installed in the outgoing feeders then one circuit-breaker is needed either on the MV or on the LV side of the transformer. In case of short-circuits on any feeder, the total load is switched off and supplied again only after isolation of the faulted line by the associated load break switch.
Recommended: The Ultimate Guide to Electrical Maintenance
This busbar arrangement is characterized by the following features:
The disadvantages presented by the single busbar without separation can be prevented by the arrangement of a busbar with a sectionalizer. In the first case the sectionalizing function is realized by a load break switch, in the second case by a circuit breaker.
Generally it is not meaningful to construct substations having two transformers with single busbar without sectionalizer. In principle with use of two transformers further arrangements of the substations are possible.
Another arrangement of a single busbar with two transformers is illustrated below:
This arrangement is characterized by the following features:
Substations with single busbar, longitudinal bus coupler and two transformers are also installed in the 110 kV systems in urban areas. The 110 kV cables are looped in and out of the substation as shown in figure 3(a)
Supposing the parameters of the line protection are set in such a way that the longitudinal bus coupler is opened in case of short-circuits on the lines, the circuit breakers in the outgoing feeders can be avoided and only load break switches are required. A similar arrangement is applied for the transformer circuit breakers where in case of faults the feeding line is switched off.
Don’t miss out on key updates, join our newsletter List
A substation arrangement without any circuit breakers is called load disconnecting substation, but this needs two load break switches in the busbar in order to be able to deenergize each section of the busbar.
The characteristic features of this arrangement are:
This arrangement is known as a three switch mesh substation as shown in figure 3(b). It utilizes only three circuit breakers to control four circuits. This scheme offers better features and facilities than a single busbar without a bus section switch.
The three switch mesh has the following features:
A development of the three switch arrangement for multiple circuit substations is the full mesh layout shown in figure 3(c). Each section of the mesh is included in a line or transformer protection zone so no specific separate busbar protection is needed. Operation of the two circuit breakers is needed to connect or disconnect a circuit; disconnection involves opening the mesh line or transformer circuit, disconnectors may then be used to isolate the specific circuit and the mesh reclosed.
This arrangement has the following features:
Related: Surge Suppression in Power Systems
The ring busbar offers increased security compared to the single busbar arrangement since the alternative power flow routes around the ring busbar are available. An example of a typical scheme that would occupy more space than a single busbar arrangement is shown below:
The ring is not secure as the mesh arrangement discussed earlier since a busbar fault causes all circuits to be lost until the fault has been isolated using the ring busbar isolators. Unless busbar disconnectors are duplicated, maintenance on a disconnector requires an outage of adjacent circuits. The inability of disconnectors to break load current is also an operation disadvantage.
Related: Switchgear
Switchgear with double busbar is a typical arrangement for grid stations in MV, HV and EHV systems. All the incoming and outgoing lines and transformers are connected with circuit breakers and disconnecting switches to the busbars as illustrated in figure 4(a)
A bus coupler consisting of a circuit breaker and disconnecting switches is required to separate the two busbars in case of busbar faults.
This arrangement offers a high degree of supply reliability and operation flexibility because each outgoing line and transformer can be switched without supply interruption from one busbar to the other if the busbars are operated in coupled mode. For separate operation of the busbars, separate network groups can be operated.
Features of Double Busbar arrangement
Related: Key Factors to Consider In Substation Design
This arrangement is very costly and therefore only advisable for very important grid stations in the HV and EHV systems. During the operation, all the three busbars are energized; the outgoing transformers and lines are connected to two busbars only whilst the third one is separated with no load and is available as a reserve busbar and for switching purposes.
This arrangement has an advantage that a busbar can be completely deenergized without reducing the operation flexibility (i.e. two busbars remain in operation). In addition, in case of a loss of one busbar due to faults, the two other busbars remain available.
Key characteristics of this arrangement are:
You can also read: Types of Insulators used in Power Systems
The importance of printed circuit board (PCB) technology has escalated throughout the years with the…
One of the key challenges in measuring the electrical current in high voltage, high power…
The Concept behind Wiegand Effect Based Sensors The Wiegand effect technology employs the unique…
An accelerometer is a sensor that is designed to measure acceleration or rate of change…
The USB-6009 is a small external data acquisition and control device manufactured by National Instruments…
X-Y tables are utilized as components in many systems where reprogrammable position control is desired.…
View Comments