The Conditioning of Thermocouple Sensor Voltages

Consider the circuit below:

Thermocouple signal amplifying circuit
Figure 1(a) thermocouple signal amplifying circuit

From the figure above, the sensing junction and reference junction are connected in series. When the junctions are at the same temperature the voltage output from the junctions is zero and the output from the amplifier is zero. When the junctions are at different temperatures, there is a differential voltage at the input to the amplifier that is then amplified and converted to a temperature reading. To make this absolute reading, the temperature of the reference junction is needed. This can be obtained by placing the junction in a constant temperature enclosure or the temperature of the reference junction can be measured and correction applied to the output reading of the thermocouple’s sensing amplifier.

The amount of signal conditioning required by a thermocouple will depend on its temperature range. The thermocouple accuracy is 1 to 2 % over a limited temperature range but requires conditioning i.e. linearization if used over its full operating range. The set zero conditioning is part of the reference temperature correction. Thermocouple voltages can also be sensed directly by the controller using an internal amplifier and then conditioned internally.

Related: Types of Sensors used in Measurement and Process Control

Thermocouple signals can be amplified with cold junction reference close to the amplifier and the signal transmitted in analog or digital format to a controller or the thermocouple can be directly connected to the controller for amplification and cold junction correction. The latter method is sometimes employed to eliminate the cost of remote amplifiers and power supplies. Controller peripheral modules are available for the amplification of several thermocouple inputs with cold junction correction.

Figure 1(b) twisted pair of wires for thermocouple sensor connection

Figure 1(b) shows a differential connection between amplifier and the thermocouple as twisted pair of wires that are shielded to minimize noise or electrical interference.

You can also read: Basics facts about Thermocouples

Share
John Mulindi

John Mulindi is an Industrial Instrumentation and Control Professional with a wide range of experience in electrical and electronics, process measurement, control systems and automation. In free time he spends time reading, taking adventure walks and watching football.

Recent Posts

Single-Ended vs. Differential Amplifiers

Most often than not, the signal from the sensor in a measurement and control or…

1 week ago

What is Corona Discharge in Power Transmission Conductors?

Corona and its Effects in Power Transmission Systems What is Corona? Corona is the term…

2 weeks ago

6 Types of Machine Guards

What is Machine Guarding? Most machines have cutting blades or rotating/moving parts that can cause…

2 weeks ago

Air Circuit Breakers: Features, Operation & Applications

Air Circuit Breaker Features & Operation An air circuit breaker employs atmospheric air as its…

2 weeks ago

Single-Phase & Three-Phase Inverters: Function and Operation

What is the Purpose of Inverters? Whereas dc machines are controlled by varying the voltage…

3 weeks ago

The Manufacturing Process Behind 6 Layers PCB Board

PCBs are a vital part of modern electronics, forming the core for links and attachment…

3 weeks ago