The Conditioning of Thermocouple Sensor Voltages

Consider the circuit below:

Thermocouple signal amplifying circuit
Figure 1(a) thermocouple signal amplifying circuit

From the figure above, the sensing junction and reference junction are connected in series. When the junctions are at the same temperature the voltage output from the junctions is zero and the output from the amplifier is zero. When the junctions are at different temperatures, there is a differential voltage at the input to the amplifier that is then amplified and converted to a temperature reading. To make this absolute reading, the temperature of the reference junction is needed. This can be obtained by placing the junction in a constant temperature enclosure or the temperature of the reference junction can be measured and correction applied to the output reading of the thermocouple’s sensing amplifier.

The amount of signal conditioning required by a thermocouple will depend on its temperature range. The thermocouple accuracy is 1 to 2 % over a limited temperature range but requires conditioning i.e. linearization if used over its full operating range. The set zero conditioning is part of the reference temperature correction. Thermocouple voltages can also be sensed directly by the controller using an internal amplifier and then conditioned internally.

Related: Types of Sensors used in Measurement and Process Control

Thermocouple signals can be amplified with cold junction reference close to the amplifier and the signal transmitted in analog or digital format to a controller or the thermocouple can be directly connected to the controller for amplification and cold junction correction. The latter method is sometimes employed to eliminate the cost of remote amplifiers and power supplies. Controller peripheral modules are available for the amplification of several thermocouple inputs with cold junction correction.

Figure 1(b) twisted pair of wires for thermocouple sensor connection

Figure 1(b) shows a differential connection between amplifier and the thermocouple as twisted pair of wires that are shielded to minimize noise or electrical interference.

You can also read: Basics facts about Thermocouples

John Mulindi

John Mulindi is an Industrial Instrumentation and Control Professional with a wide range of experience in electrical and electronics, process measurement, control systems and automation. In free time he spends time reading, taking adventure walks and watching football.

Recent Posts

How AI and Machine Learning are Enhancing Electrical Control Processes

Electrical control processes form the backbone of industries, enabling seamless operations across sectors like manufacturing,…

2 days ago

Standard Process Signals for Industrial Instrumentation

Industrial measurement and control processes employ standard process signals that are used throughout all the…

2 weeks ago

Top 5 Benefits of Combining CCTV Cameras with Biometric Systems

The integration of advanced technologies in security systems has become imperative for ensuring safety and…

2 weeks ago

Sources of Power Quality Problems

Power quality may be affected by a number of issues. Our discussion in this article…

2 weeks ago

Common Terms Used When Describing Power Quality Problems

Power quality has become an important issue to electricity consumers at all levels of consumption.…

2 weeks ago

What to Expect from PCB Assembly Services in China

The importance of printed circuit board (PCB) technology has escalated throughout the years with the…

3 weeks ago