How to Connect a DP (Differential Pressure) Flow Sensor to a DP Transmitter

The DP Transmitter should be mounted with a manifold block as illustrated in the figure 1(a) below to allow for maintenance.

Connection of a DP flow sensor to a DP transmitter
Figure 1(a) connection of a DP flow sensor to a DP transmitter

Valves B and C are the isolation valves while valve A is an equalizing valve. Valve A is used along with valves B and C to zero the transmitter.

In normal operation valve A is closed and valves B and C are open. Valve A should always be opened before valves B and C are closed prior to the removal of the transducer/transmitter to avoid high pressure being locked into one leg. Similarly on replacement, valves B and C should be opened before valves A is closed to prevent damage from static pressure.

Gas measurements are prone to condensate in pipes and liquid measurements are prone to gas bubbles. To prevent these effects, a gas differential transducer/transmitter should be mounted above the pipe and a liquid differential transducer/transmitter should be mounted below the pipe with tap off points in the quadrants as illustrated in figure 1(b) and 1(c) below. Ideally the piping should be taken from the top of the pipe and rise to the transducer/transmitter for gas systems, and be taken from the lower half of the pipe and fall to the transducer/transmitter for liquid pressure measurement.  If this is not possible, vent/drain cocks must be fitted. Under no circumstances should the piping form traps where gas bubbles or liquid sumps form.

Figure 1(b) gas pressure transducer/transmitter above the pipe

Figure 1(c) liquid pressure transducer/transmitter below the pipe

Steam pressure transmitters are a special case. Since steam can damage the pressure transmitter diaphragm, the piping leg to the pressure transmitter is normally arranged to naturally fill with water by taking the tapping of the top of the pipe and mounting the transmitter with (unlagged pipes) below the pipe as shown in figure 1(d). If this is not possible a steam trap is placed in the piping as illustrated in figure 1(e). In both cases there will be an offset from the liquid head, a similar effect occurs when a liquid pressure transmitter is situated below the pipe. In both of these cases, the offset pressure is normally removed in the transmitter set up and configuration.

Figure 1(d) preferred piping arrangement for steam pressure transmitter installation

Figure 1(e) Alternative arrangement for steam pressure transmitter installation

Pressure transmitters require maintenance or may need to be replaced altogether, so isolation valves should always be fitted. These should include an automatic vent on closure so pressure cannot be locked into the pipe between the transmitter and the isolation valve.

You can also read: P&IDs and Loop Diagrams

While the accuracy (around 4%) and turndown (4:1) of differential pressure flowmeters is poor, their robustness, low cost and ease of installation makes them a frequent choice for industrial flow applications.

Share
John Mulindi

John Mulindi is an Industrial Instrumentation and Control Professional with a wide range of experience in electrical and electronics, process measurement, control systems and automation. In free time he spends time reading, taking adventure walks and watching football.

View Comments

Recent Posts

What to Expect from PCB Assembly Services in China

The importance of printed circuit board (PCB) technology has escalated throughout the years with the…

2 days ago

Magneto-Optic Current Sensors for High Voltage, High Power Transmission Lines

One of the key challenges in measuring the electrical current in high voltage, high power…

4 days ago

How the Wiegand Effect is used in Sensing Instruments

The Concept behind Wiegand Effect Based Sensors   The Wiegand effect technology employs the unique…

6 days ago

Piezoelectric Accelerometer: Principle of Operation & Applications

An accelerometer is a sensor that is designed to measure acceleration or rate of change…

1 week ago

The USB-6009 Data Acquisition Card Features

The USB-6009 is a small external data acquisition and control device manufactured by National Instruments…

1 week ago

How X-Y Tables are used in Position Control Applications

X-Y tables are utilized as components in many systems where reprogrammable position control is desired.…

2 weeks ago