Features of Analog Signal Transmission

Analog voltage or current signals are hardwired between the transmitter and the receiver. These analog signals can be relatively be slow to settle compared to digital signals, due time constant of the lead capacitance, inductance and resistance.

Analog signals can lose accuracy if the signal lines are long with high resistance. These signals can be susceptible to ground offset, ground loops, EMI noise from transmitters & motors and radio frequency pick-up.

To reduce these problems, the following precautions should be taken:

  • The ground connection is used only for the signal return path.
  • The dc supply to the transmitter is generated from the AC line via an isolation transformer and voltage regulators, to minimize noise from the power supply.
  • The signal and ground return leads are a screen twisted pair, with the screen grounded at one end only as illustrated below:
Shielded differential signal connection between the controller and the transmitter
Figure 1(b) Screened/shielded differential signal connection between the controller and the transmitter

The Radio Frequency (RF) and Electromagnetic interference (EMI) noise pickup are reduced by the screen and the induced noise in both lines is greatly reduced. Because variations, in the supply voltages can produce changes in the offset voltage and the gain of the sensor/transmitter, the supply must be regulated.

The reduced pickup affects both signals by the same amount and will cancel in the differential receiver in the controller. Differential signals are not normally affected by ground offsets.

Related: Sources of Noise in Measurement Systems

Voltage Signals

The voltage signals are usually standardized in the voltage ranges 0 to 5 V, 0 to 10 V, or 0 to 12 V, with the 0 to 5 V being the most common.

The requirements of the transmitter are a low output impedance to enable the amplifier to drive a wide range of loads without a change in the output voltage. Other transmitter’s requirements are low temperature drift, low offset drift, and low noise.

Related: 4-20 mA Transmitters (2-wire, 3-wire and 4-wire Types)

Current Signals

Current signals are standardized in the ranges i.e. 4-20 mA and 10 to 50 mA where 0 mA is a fault condition. The latter range was the preferred standard but it was dropped, and the 4-20 mA is the accepted standard. The requirements of the transmitter are high output impedance, so that the output current does not vary with load, low temperature, offset drift, and low electrical noise.

Don’t miss out on key updates, join our newsletter  List

The main disadvantage of the current signal is the longer settling time due to the high output impedance of the driver, which limits the current available to charge up the line capacitance.

Figure 1(b) effect of resistance and lead capacitance on current signals

The signal current at the controller after the line capacitance is charged is the same as the signal current at the transmitter and is not affected by normal changes in lead resistance. The internal resistance of the controller is low for current signals e.g. a few hundred ohms, which helps to lower the time constant of the transmission line.

John Mulindi

John Mulindi is an Industrial Instrumentation and Control Professional with a wide range of experience in electrical and electronics, process measurement, control systems and automation. In free time he spends time reading, taking adventure walks and watching football.

View Comments

Recent Posts

How Metal Fabrication is Powering the EV Revolution

Image: Pexels The electric vehicle (EV) market is accelerating at an unprecedented pace, driven by…

1 week ago

Basic Features of Numerical Control

Numerical control is a form of digital control that is employed on machine tools such…

2 weeks ago

Benefits of Installing Solar Panels in Your Home

Photo: Pexels Benefits of Installing Solar Panels in Your Home: Save Money and Your Planet…

3 weeks ago

How to Size a Control Valve

Pneumatic control valve Control valve sizing refers to the procedure determining the correct size of…

3 weeks ago

Process Control System Design for a Distillation Unit

The aim of a typical control system is to force a given set of process…

3 weeks ago

Limit Switches vs. Proximity Sensors

An object can be used to activate a switch directly, producing an ON or OFF…

3 weeks ago