Mastering Electrical, Process Measurement & Control Systems

Home » Process Plants Instrumentation » How to Size a Control Valve

How to Size a Control Valve

Pneumatic control valve
Pneumatic control valve

Control valve sizing refers to the procedure determining the correct size of a valve body. A valve sizing equation for incompressible fluids is given by:

Control valve sizing

Which is the same as:

Control valve sizing

Where Cv is the valve flow coefficient/valve capacity

P1 = Upstream fluid pressure

P2 = Downstream fluid pressure

ρ = Mass density of fluid

Q = Volumetric fluid flow rate

∆P = The pressure drop across the valve

Alternatively the above equation is sometimes written as:

Control valve sizing

Where G is the specific gravity, Cv i.e. valve capacity (in US) is defined as the number of gallons per minute of water that will flow through a valve with 1 PSI of pressure drop. Elsewhere in the world, valve capacity is defined as the amount of cubic meters per hour of water that will flow through a valve with a pressure drop of 1 bar, symbolized as Kv.

The above equations can be written with the quantities in SI units:

Control valve sizing

Alternatively, it may be written as:

Control valve sizing

The last two forms of the equation derive from its original specification in terms of US gallons.

The table below shows typical values of Av, Cv and valve size:

Table 1.0: Flow Coefficients and Valve Sizes

Flow Coefficients                             Valve Size (mm)
4806408009601260160019202500
CV81422305075110200
Av x 10-519335271119178261474

Example: Consider the problem of determining the size of a valve that is required to control the flow of water when the maximum flow required is 0.012 m3/s and the permissible pressure drop across the valve at this flow rate is 300 kPa.

Solution

Using this equation

Control valve sizing

Then, since the density of water is 1000 kg/m3,

Control valve sizing

Using table 1.0 above, the valve size is 960 mm.

The flow coefficient of a control valve Cv as indicated earlier is a numerical value expressing the number of gallons per minute flow of water the valve will pass with a constant pressure drop of 1 PSI from inlet to outlet. This rating is normally given for the valve in its wide open state. For instance, a control valve with a Cv rating of 50 should flow 50 gallons per minute of water through it with a 1 PSI pressure drop when wide open. The flow coefficient value for this same control valve will be less than 50 when the valve position is anything less than fully open. When the control valve is in the fully shut position, its Cv value will be zero. Therefore, Cv is variable not a constant for any control valve, though control valves are often specified simply by their maximum flow capacity. It is thus important that any control valve sized large enough (possess adequate maximum Cv capacity) to flow the greatest expected flow rate in any given process installation. If you select a valve that is too small for an application, it will not be able to pass adequate process fluid through it when required. When selecting a valve, it is important to consider the valve style, inherent characteristics and valve size that will offer the broadest possible range for the application.

Related Articles:

Please follow us & share:

Comments

Currently trending: