The USB-6009 is a small external data acquisition and control device manufactured by National Instruments that is normally connected to a computer through a USB port. It is used in applications such as simple data logging, academic lab experiments and portable measurements. This device has analogue to digital (A/D) conversion capabilities as well as digital to analogue (D/A) conversion, digital I/O, and counters/timers.
The I/O lines are connected with wire (16-28 AWG) to the detachable screw terminals. As indicated in the tables 1.0, 1.1 and 1.2 below, screw terminals 1-16 are used for analog I/O, and terminals 17-32 are used for digital I/O and counter/timer functions.
Take note of the fact, analog terminals are different depending on which mode the device is in: single-ended mode (also referred to as RSE) or differential mode. In single-ended mode the positive voltage signal is connected to an AI terminal and the negative voltage or ground signal is connected to a GND terminal. This mode utilizes two terminals, implying that they are eight analog inputs available (AI 0 – AI 7). There are two analog outputs AO 0 and AO 1. The maximum voltage range in this mode is -10 V to 10 V.
Differential mode can be used to get a larger voltage range. This mode measures the difference between two signals, AI+ and AI-, each referenced to GND. A voltage range of -20 V to 20 V can be attained, however the maximum voltage on one pin (AI+ or AI-) referenced to ground is ±10 V. Differential mode uses one more wire than single-ended mode, thus only four analog inputs are available in this mode. One more difference between differential and single-ended mode is the resolution of the analog inputs. Differential mode has a resolution of 14 bits where single-ended mode has a resolution of 13 bits.
Table 1.0: USB-6009 Pin Assignments, Analog (1-16)
Terminal | Signal (Single-Ended Mode) | Signal (Differential Mode) |
1 | GND | GND |
2 | AI 0 | AI 0+ |
3 | AI 4 | AI 0- |
4 | GND | GND |
5 | AI 1 | AI 1+ |
6 | AI 5 | AI 1- |
7 | GND | GND |
8 | AI 2 | AI 2+ |
9 | AI 6 | AI 2- |
10 | GND | GND |
11 | AI 3 | AI 3+ |
12 | AI 7 | AI 3- |
13 | GND | GND |
14 | AO 0 | AO 0 |
15 | AO 1 | AO 1 |
16 | GND | GND |
Table 1.1: USB-6009 Pin Assignments, Digital (17-32)
Recommended: The Ultimate Guide to Electrical Maintenance
Terminal | Signal |
17 | P0.0 |
18 | P0.1 |
19 | P0.2 |
20 | P0.3 |
21 | P0.4 |
22 | P0.5 |
23 | P0.6 |
24 | P0.7 |
25 | P1.0 |
26 | P1.1 |
27 | P1.2 |
28 | P1.3 |
29 | PFI 0 |
30 | +2.5 V |
31 | +5 V |
32 | GND |
The analog input converter type is successive approximation and the maximum sampling rate is 48 thousand samples per second (kS/s). This device contains one analog-to-digital converter that is multiplexed to each input. Lastly this device supports USB 2.0 full-speed interface.
Table 1.2: USB-6009 Pin Signal Descriptions
Signal Name | Reference | Direction | Description |
GND | – | – | Ground – The reference point for single-ended AI measurements, bias current return point for differential mode measurements, AO voltages, digital signals at the I/O connector, +5 VDC supply and the +2.5 VDC reference. |
AI<0..7> | Varies | Input | Analog Input Channels 0 to 7 – For single-ended measurements, each signal is an analog input voltage channel. For differential measurements, AI 0 and AI 4 are the positive and negative inputs of differential analog input channel 0. The following signal pairs also form differential input channels: <AI 1, AI 5>, <AI 2, AI 6>, and <AI 3, AI 7>. |
AO 0 | GND | Output | Analog Channel 0 Output – Supplies the voltage output of AO channel 0. |
AO 1 | GND | Output | Analog Channel 1 Output – Supplies the voltage output of AO channel 1. |
P1.<0..3> P0.<0..7> | GND | Input or Output | Digital I/O signals – You can individually configure each signal as input or output. |
+2.5 V | GND | Output | +2.5 V External Reference – Provides a reference for wrap-back testing. |
+5 V | GND | Output | +5 V Power Source – Provides +5V power up to 200 mA. |
PFI 0 | GND | Input | PFI 0 – This pin is configurable as either a digital trigger or an event counter input. |
You may also read:
- Basic Facts about Data Acquisition (DAQ) and Process Control
- Features of Analog Signal Transmission
- NAMUR NE 107 Standard for Modern Instrumentation Diagnostics
- The IEEE-488 Instrumentation Bus (GPIB)
- CAMAC (IEEE-583) Modular Instrumentation Standard
- Supervisory Control and Data Acquisition in Power Systems
- Data Acquisition and Telemetering in Power Systems
Comments