Contents
Initially signal transmission was dominated by pneumatics before the advent of 4-20 mA signal standard. The standard was 3-15 psi pneumatic signal where the 3 psi was the ‘live zero’ and 15 psi represented the 100 %. Any pressure below 3 psi was considered ‘dead zero’ and an alarm condition. Large compressors drove the 3 -15 psi pneumatic signals throughout the plant, and these pneumatic lines connected to pneumatically controlled valves to drive proportional controls and actuators throughout the plant. With the advent of computerized process control, in the early 1950’s the signal transmission technique shifted from 3-15 psi to 4-20 mA signals where the 4 mA was the ‘live zero’. Note that the ‘real’ dead zero has always been the alarm condition.
Nevertheless, some industrial installations still use pneumatic control today, especially in applications where electrical signals or sparks could ignite combustible materials. Modern I/P converters (current-to-pressure transducers) are available to convert the 4-20 mA current loops to common pneumatic signal ranges 3-15 psi, 1-18 psi, and 6-30 psi and P/I converters (pressure-to-current) that convert pneumatic signals to current signals.
Figure 1(a) below shows the internal circuit blocks of a 4-20 mA transmitter.
These circuits provide the following functions as illustrated by the block diagram above:
Consider the current loop schematic diagram below:
An ideal Norton current source composed of IS and RS signal models the 4-20 mA transmitter. The line resistance is given as RL and VN represents the random induced loop noise in form of voltage. In this application example, the 500 ohm controller and 240 ohm digital display are connected with the signal current. The loop is powered by a 24 V DC supply.
You can notice that, the loop noise at a load is reduced by the factor
Recommended: The Ultimate Guide to Electrical Maintenance
(V supply – all load voltages –line IR drops)
Therefore the compliance voltage or loop power supply voltage must be greater than the maximum voltage in the loop. There are 3 things that must be checked when determining loop compliance or power supply voltage:
-The compliance voltage should be able to power all the devices in the loop.
Don’t miss out on key updates, join our newsletter List
-The loop power supply should not exceed the maximum voltage rating of any device in the loop.
We have 3 types of 4-20 mA transmitters, namely:
In 2-wire 4-20 mA current loops, we use 2-wire transmitters to convert the various process signal representing flow, level, position, pressure, strain, temperature, pH, speed, etc. to 4-20 mA dc for the purpose of transmitting the signal over some distance with little or no loss signal noise.
The figure 1(c) below, illustrates the 2-wire transmitter energized by the loop current.
How to Access Our Premium Articles & Resources Learn More
You can notice from figure 1(c), that the transmitter floats relative to the ground and the dc power in series in the loop. Power supply and receiver shares a common, which is connected to the ground. Note we can only have one ground in 4-20 mA system. Multiple grounds will cause errors in the readings.
The transmitter and receiver shares common with power supply. We have a separate dc power connection to the transmitter.
The transmitter and receiver floats. A separate power supply powers the transmitter.
Please note, in most instrumentation installations, the power supply is local either to the transmitter or the receiver.
The floating connection relative to the ground in the 2-wire transmitters makes them flexible in the way they connect to various receiver devices. The receiver devices can be connected as either sourcing inputs or sinking inputs. Sourcing inputs act as loop receivers and source of current in the loop as illustrated in figure 1(f)
Sinking units do not provide the excitation for the transmitter hence they need a separate power supply in the loop as illustrated in figure 1(g).
Since in most installations the loop power is either local to the transmitter or local to the remote receiver, a shielded pair wiring is often used to connect the longest distance between the field transmitter and remote receiver. The twisted pair provides protection against electrical noise that might cause errors in measurement.
You can also read: Types of Sensors used in Measurement and Process Control
Image: Pexels The electric vehicle (EV) market is accelerating at an unprecedented pace, driven by…
Numerical control is a form of digital control that is employed on machine tools such…
Photo: Pexels Benefits of Installing Solar Panels in Your Home: Save Money and Your Planet…
Pneumatic control valve Control valve sizing refers to the procedure determining the correct size of…
The aim of a typical control system is to force a given set of process…
An object can be used to activate a switch directly, producing an ON or OFF…
View Comments